Letters shall have a minimum height of 2 inches 51 mm with a minimum stroke of 3 8 inch 10 mm.
Fire riser room door requirements.
The international codes i codes are the widely accepted comprehensive set of model codes used in the us and abroad to help ensure the engineering of safe sustainable affordable and resilient structures.
Access doors for automatic sprinkler system riser rooms and fire pump rooms shall be labeled with an approved sign.
And that stairwell has an exterior door.
Doors to any fire protection electrical or mechanical equipment rooms shall be marked from the exterior.
If the room has a lock then the.
This standard regulates the installation and maintenance of assemblies and devices used to protect openings in walls floors and ceilings against the spread of fire and smoke within into or out of buildings.
Fire protection equipment access signs sprinkler room fire pump room fire pump test valve etc should be marked with white letters on a red background.
Door marking requirements code section.
1 1 1 with the exception of fabric fire safety curtain assemblies this standard addresses assemblies that have.
Access doors for automatic sprin kler system riser rooms and fire pump rooms shall be labeled with an approved sign.
The international code council icc is a non profit organization dedicated to developing model codes and standards used in the design build and compliance process.
The fire sprinkler riser assembly the fire alarm control panel fire alarm manual pull station spare sprinkler heads storage box and the document box for as built drawings shall be located within the room.
I was going to add that i have heard of one project that our office designed and the fpe that the contractor hired put the fire riser in the stairwell and got approved by the state fire marshal.
901 4 6 2 marking on access doors.
The lettering shall be in a contrasting color to the background.
Cated in a fire pump room or automatic sprinkler system riser room the door shall be permitted to be locked provided the key is available at all times.
That is the only project that i know of that has it in the stairwell.
Fire pumps may also be kept within the riser room though the room will then have to meet the more robust construction requirements for pump rooms as set by nfpa 20 fire protection storage cabinet often the riser room serves as an ideal location to store spare sprinkler heads compatible sprinkler wrenches copies of relevant nfpa codes.
What s new is fire pumps controllers and risers shall be readily accessible within the room and to those who access the room.